Governor Model: TGOV3 and TGOV3D

 

Model Equations and/or Block Diagrams

   

Parameters for TGOV3:

Trate Turbine rating, MW
K Governor gain (recirpocal of droop), pu
T1 Governor lead time constant, sec
T2 Governor lag time constant, sec
T3 Valve positioner time constant, sec
Uo Maximum valve opening velocity, pu/sec
Uc Maximum valve closing velocity, pu/sec
Pmax Maximum valve opening, pu of mwcap
Pmin Minimum valve opening, pu of mwcap
T4 Inlet piping/steam bowl time constant, sec
K1 Fraction of hp shaft power after first boiler pass
T5 Time constant of second boiler pass (i.e. reaheater), sec
K2 Fraction of lp shaft power after first boiler pass
T6 Time constant of crossover of third boiler pass, sec
K3 Fraction of hp shaft power after second boiler pass
Ta Time to close Intercept Valve (IV), sec
Tb Time until Intercept Valve starts to reopen, sec
Tc Time until Intercept Valve is fully open, sec
Prmax Maximum pressure in reheater, pu
Gv1 Nonlinear gain point 1, pu gv
Pgv1 Nonlinear gain point 1, pu power
Gv2 Nonlinear gain point 2, pu gv
Pgv2 Nonlinear gain point 2, pu power
Gv3 Nonlinear gain point 3, pu gv
Pgv3 Nonlinear gain point 3, pu power
Gv4 Nonlinear gain point 4, pu gv
Pgv4 Nonlinear gain point 4, pu power
Gv5 Nonlinear gain point 5, pu gv
Pgv5 Nonlinear gain point 5, pu power
Gv6 Nonlinear gain point 6, pu gv
Pgv6 Nonlinear gain point 6, pu power

Parameters for TGOV3D:

K Governor gain (recirpocal of droop), pu
T1 Governor lead time constant, sec
T2 Governor lag time constant, sec
T3 Valve positioner time constant, sec
Uo Maximum valve opening velocity, pu/sec
Uc Maximum valve closing velocity, pu/sec
Pmax Maximum valve opening, pu of mwcap
Pmin Minimum valve opening, pu of mwcap
T4 Inlet piping/steam bowl time constant, sec
K1 Fraction of hp shaft power after first boiler pass
T5 Time constant of second boiler pass (i.e. reaheater), sec
K2 Fraction of lp shaft power after first boiler pass
T6 Time constant of crossover of third boiler pass, sec
K3 Fraction of hp shaft power after second boiler pass
Ta Time to close Intercept Valve (IV), sec
Tb Time until Intercept Valve starts to reopen, sec
Tc Time until Intercept Valve is fully open, sec
Prmax Maximum pressure in reheater, pu
dbH Deadband High (pu)
dbL Deadband Low (pu)
Trate Turbine rating, MW